PSTX142-690-70, ABB, Softstarter, 125 Hp, 690V, Control 120-250V, IP20
ABB Softstart General Information
-
- Global Commercial Alias:
- PSTX142-690-70
-
- Extended Product Type:
- PSTX142-690-70
-
- Product ID:
- 1SFA898210R7000
-
- ABB Type Designation:
- PSTX142-690-70
-
- EAN:
- 7320500501450
-
- Catalog Description:
- PSTX142-690-70 Softstarter
-
- Long Description:
- Softstarter PSTX142-690-70 for max 690V main voltage and 100 - 250V 50/60Hz control supply voltage.
-
Dimensions
-
- Product Net Width:
-
199.000 mm
-
- Product Net Height:
-
377.000 mm
-
- Product Net Depth / Length:
-
235.000 mm
-
- Product Net Weight:
-
9.60 kg
Technical
-
- Rated Operational Voltage:
- 208 … 690 V AC
-
- Rated Control Supply Voltage (Us):
- 100 … 250 V AC
-
- Rated Control Circuit Voltage (Uc):
- DC Operation 24 V
-
- Rated Frequency (f):
- Main Circuit 50/60 Hz
-
- Rated Operational Power - In-Line Connection (Pe):
- (230 V) 37 kW
(400 V) 75 kW
(500 V) 90 kW
(690 V) 132 kW
-
- Rated Operational Current - In-Line Connection (Ie):
- 142 A
-
- Rated Operational Power - Inside Delta Connection:
- at 230 V 75 kW
at 400 V 132 kW
at 500 V 160 kW
at 690 V 220 kW
-
- Rated Operational Current - Inside Delta Connection:
- 245 A
-
- Service Factor Percentage:
- 100 %
-
- Overload Protection:
- Build-in electronic overload protection
-
- Integrated Electronic Overload:
- Yes
-
- Starting Capacity at Maximum Rated Current Ie:
- 4xIe for 10s
-
- Ramp Time:
- 1 ... 120 second [unit of time]
-
- Initial Voltage During Start:
- 10 ... 99 %
-
- Step Down Voltage Special Ramp:
- 100 ... 10 %
-
- Current Limit Function:
- 1.5 … 7.5 xle
-
- Switch for Inside Delta Connection:
- Yes
-
- Run Signal Relay:
- Yes
-
- By-pass Signal Relay:
- Yes
-
- Fault Signal Relay:
- Yes
-
- Overload Signal Relay:
- Yes
-
- Analog Outputs:
- 0…10 V, 0…20 mA, 4…20 mA
-
- Signal indication ready to start/standby ON (LED):
- Green
-
- Signal indication running R (LED):
- Green
-
- Signal indication protection (LED):
- Yellow
-
- Signal indication fault (LED):
- Red
-
- Communication:
- Built in Modbus interface, Anybus, FieldBusPlug (with adapter).
-
- Degree of Protection:
- acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
-
- Terminal Type:
- Main Circuit: Bars
-
- Connecting Capacity Main Circuit:
- Hole Diameter 8.5 mm
-
- Connecting Capacity Control Circuit:
- Rigid 1x2.5 mm²
-
- Connecting Capacity Supply Circuit:
- Rigid 1x2.5 mm²
-
- Tightening Torque:
- Main Circuit 14 N·m
-
- Product Main Type:
- PSTX142
Environmental
-
- Ambient Air Temperature:
- Storage -40 ... +70 °C
Operation -25 ... +60 °C
-
- RoHS Status:
- Following EU Directive 2002/95/EC August 18, 2005 and amendment
Certificates and Declarations (Document Number)
-
- CQC Certificate:
-
CN: CQC2014010304744407 / SE: CQC2014010304724379
-
- Declaration of Conformity - CCC (CCC):
-
CN: 2020980304001092 / SE: 2020980304001485
-
- Declaration of Conformity - CE:
-
2CMT005209
-
- Environmental Information:
-
2CMT005232
-
- Instructions and Manuals:
-
1SFC132081M0201
-
- RoHS Information:
-
2CMT005210
Container Information
-
- Package Level 1 Width:
- 280 mm
-
- Package Level 1 Depth / Length:
- 455 mm
-
- Package Level 1 Height:
- 315 mm
-
- Package Level 1 Gross Weight:
- 10.40 kg
-
- Package Level 1 EAN:
- 7320500501450
-
- Package Level 1 Units:
- 1 piece
Classifications
-
- Object Classification Code:
- Q
-
- ETIM 4:
- EC002572 - Electronic motor control and protection device
-
- ETIM 5:
- EC002572 - Electronic motor control and protection device
-
- ETIM 6:
- EC002572 - Motor management device
-
- UNSPSC:
- 39121521
-